Mikro MK330A Self-Reclosing Earth Leakage Relay User's Manual

User manual for the Mikro MK330A self-reclosing earth leakage relay: settings, indicators, output contacts, fault records and technical data.


Mikro MK330A Self-Reclosing Earth Leakage Relay User's Manual - cover page
Brand
Mikro
Category
RELAY
Document type
User Manual
Language
English
Pages
2
File format
PDF
File size
2.4 MB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
1F33264504135329E9A44D508D174CDA

About this manual

The Mikro MK330A is a microprocessor-based earth leakage relay with a built-in self-reclosing function. A zero-phase current transformer (ZCT) connected to the relay senses the leakage current, and the self-reclosing module provides a settable number of reclose operations while distinguishing transient faults from persistent faults.

The manual explains the front-panel indicators, push-button operation, the digital input port, the trip safe and programmable output contacts, the self-reclose terms (shots, dead time, persistent fault time, reclaim time and lockout auto reset time), fault record handling, technical data, the connection diagram and the case dimensions.

What's inside

  • Description
  • Light Indicators
  • Push Buttons Operation
  • Digital Input Port
  • Output Contacts
  • Self-Reclose
  • Records
  • Technical Data
  • Connection Diagram
  • Case Dimension

Specifications

Auxiliary supplyMK330A-230A: 184~276 VAC; MK330A-110A: 94~127 VAC
Rated frequency50Hz or 60Hz
Sensitivity adjustment30mA, 50mA, 0.10~1.00A (step=50mA), 1.00~10.0A (step=1.00A)
Delay time adjustmentInstantaneous, 0.1~3.0s (step=0.1s)
Number of shots0~30 (step=1); 0 = disable reclose function
Dead time1~500sec (step=1sec)
Output contact rating5A (NO) / 3A (NC) / AC1; change over arrangement
Expected mechanical life5,000,000 operations
MountingStandard DIN 96x96mm panel mounting
Approximate weight0.58kg (excluding ZCT)

Frequently asked questions

How do I perform a trip test on the MK330A?

Press the [TEST] button and hold it for 3.5s. The first 2s simulate the pre-fault alarm condition, followed by 1.5s testing of the trip time delay, after which the relay trips.

How do I clear the fault records on the relay?

When the relay is healthy, press [RESET] to step to the most recent trip fault record, then press the up and down buttons simultaneously and hold for 3.5s until [DATA] shows "0".

How is the relay reset remotely through the digital input port?

The digital port is used to remotely reset the relay when it is tripped, locked out or has a ZCT connection fault. To reset, make a connection between terminals 5 and 6 of the relay.

What is the dead time of the self-reclosing function?

Dead time is the time from when the trip safe contact de-activates due to a leakage fault or manual test trip until it is activated again by the recloser. It is adjustable from 1~500sec in steps of 1sec.

Download PDF (2.4 MB)