User manual for the Mikro MK330A self-reclosing earth leakage relay: settings, indicators, output contacts, fault records and technical data.
The Mikro MK330A is a microprocessor-based earth leakage relay with a built-in self-reclosing function. A zero-phase current transformer (ZCT) connected to the relay senses the leakage current, and the self-reclosing module provides a settable number of reclose operations while distinguishing transient faults from persistent faults.
The manual explains the front-panel indicators, push-button operation, the digital input port, the trip safe and programmable output contacts, the self-reclose terms (shots, dead time, persistent fault time, reclaim time and lockout auto reset time), fault record handling, technical data, the connection diagram and the case dimensions.
| Auxiliary supply | MK330A-230A: 184~276 VAC; MK330A-110A: 94~127 VAC |
|---|---|
| Rated frequency | 50Hz or 60Hz |
| Sensitivity adjustment | 30mA, 50mA, 0.10~1.00A (step=50mA), 1.00~10.0A (step=1.00A) |
| Delay time adjustment | Instantaneous, 0.1~3.0s (step=0.1s) |
| Number of shots | 0~30 (step=1); 0 = disable reclose function |
| Dead time | 1~500sec (step=1sec) |
| Output contact rating | 5A (NO) / 3A (NC) / AC1; change over arrangement |
| Expected mechanical life | 5,000,000 operations |
| Mounting | Standard DIN 96x96mm panel mounting |
| Approximate weight | 0.58kg (excluding ZCT) |
Press the [TEST] button and hold it for 3.5s. The first 2s simulate the pre-fault alarm condition, followed by 1.5s testing of the trip time delay, after which the relay trips.
When the relay is healthy, press [RESET] to step to the most recent trip fault record, then press the up and down buttons simultaneously and hold for 3.5s until [DATA] shows "0".
The digital port is used to remotely reset the relay when it is tripped, locked out or has a ZCT connection fault. To reset, make a connection between terminals 5 and 6 of the relay.
Dead time is the time from when the trip safe contact de-activates due to a leakage fault or manual test trip until it is activated again by the recloser. It is adjustable from 1~500sec in steps of 1sec.