The MPM4120 pressure transmitter manual provides specifications, installation, wiring, and maintenance instructions for the Mack Sensor device.
This manual introduces the MPM4120 pressure transmitter, detailing its performance specifications, physical dimensions, and recommended installation practices. It also outlines the required electrical connections and provides guidance on unpacking, kit contents, and proper storage conditions.
Further sections cover operation procedures, routine maintenance tips, and warranty information, ensuring reliable performance in various industrial environments. This manual is written in Chinese.
| Measurement range (B type) | 0 kPa – 3.5 MPa |
|---|---|
| Measurement range (B/C type) | 0 kPa – 20 MPa |
| Supply voltage (B type) | 5 ± 0.1 VDC |
| Supply voltage (B/C type) | 8 V – 28 VDC |
| Output signal (three‑wire, B type) | 0.5 V – 4.5 VDC |
| Output signal (two‑wire, B type) | 4 mA – 20 mA |
| Output signal (three‑wire, B/C type) | 1 V – 5 VDC |
| Operating temperature (B type) | -40 °C – 125 °C |
| Operating temperature (C type) | -20 °C – 85 °C |
| Accuracy | Class 1.0 |
| Stability | ≤ ±0.5 %FS |
| Over‑pressure rating | 1.5 × full‑scale pressure |
| Vibration resistance | 10 g, 55 Hz–2000 Hz |
| Shock resistance | 100 g, 11 ms |
| Insulation resistance | >10 MΩ at 500 VDC |
| Protective rating | IP65 |
| Material compatibility | Al2O3 fluorosilicone rubber; 1Cr18Ni9Ti stainless steel |
The B‑type transmitter can be powered with 5 ± 0.1 VDC, while both B‑type and C‑type models accept 8 V to 28 VDC.
Mount the sensor on a flat, perpendicular surface and use the sealing gasket provided; avoid using Teflon tape for B‑type units and do not overtighten the fitting.
The manufacturer provides a one‑year warranty from the date of shipment for defects in materials and workmanship.