The MPM426WPF level transmitter manual provides specifications, installation, wiring, operation, and maintenance instructions.
The MPM426WPF level transmitter is a fully welded, submersible, diffusion‑silicon level measurement instrument that uses a piezoresistive OEM pressure sensor and a dedicated digital compensation circuit. It is housed in stainless steel, sealed to IP68, and suitable for oil fluid pressure detection and control.
The manual covers safety precautions, performance specifications, dimensions, installation methods for static and dynamic water, electrical connection details, unboxing, storage, operation, maintenance, fault diagnosis, and warranty information. This manual is written in Chinese.
| Measurement range | 0mH2O~2mH2O/3.5mH2O/5mH2O/10mH2O/20mH2O/35mH2O |
|---|---|
| Overload | 1.5× full‑scale pressure |
| Pressure type | Gauge pressure |
| Supply voltage | 9V–28VDC or 5VDC |
| Output signal | 0.5V–4.5VDC (3‑wire) |
| Accuracy | ±1 %FS (≤3.5 mH₂O); ±0.5 %FS (>3.5 mH₂O) |
| Comprehensive error | ±2 %FS (≤3.5 mH₂O, –20 °C–75 °C) |
| Long‑term stability | ≤±0.3 %FS/year |
| Working temperature | -20 °C to 80 °C |
| Storage temperature | -20 °C to 85 °C |
| Insulation resistance | 100 V/100 MΩ |
| Load resistance | ≥10 kΩ |
| Protection rating | IP68 |
| Weight | ≈260 g (without cable), cable ≈70 g/m |
Install the transmitter vertically downward; for dynamic water, keep the sensing face parallel to the water flow and follow the static‑water or dynamic‑water installation guidelines shown in the figures.
The device must be installed with no power and no pressure, and the installation steps must be performed by qualified technical personnel.
The transmitter can be powered by 9 V to 28 V DC or by a 5 V DC source.
First disconnect power, then re‑check the installation, wiring, power current, and ensure the vent tube is unobstructed. If the problem persists, the transmitter may be damaged and should be contacted for service.