About this manual

This manual provides complete instructions for installing, configuring, and maintaining the D350 digital voltage regulator used with alternators. It includes safety measures, wiring diagrams, mounting details, and step‑by‑step procedures for both analogue and digital operation modes.

The document also describes the NFLink™ configuration module, software setup with EasyReg Advanced, and a comprehensive troubleshooting appendix that lists common faults and corrective actions.

What's inside

  • General Instructions
  • Technical Characteristics
  • Dimensions and Mounting
  • Wiring and Connections
  • Operation Instructions
  • Setting Instructions and Software
  • Appendices
  • Fault Troubleshooting

Specifications

Regulation accuracy+/-0.25% (harmonic distortion <5%)
Voltage adjustment range0 to 150% of rated voltage
Power supply (AC)50‑277 V ac, max 3000 VA
Dimensions (H×W×L)52.9 mm × 125 mm × 140 mm
Weight0.45 kg
Frequency range10‑100 Hz
Field current rating0‑5 A continuous, 10 A short‑circuit (10 s)

Frequently asked questions

What safety steps must be taken before using the D350 regulator?

Read the entire installation and maintenance manual and ensure that all operations are performed by a qualified technician.

How is the NFLink™ configuration module attached to the regulator?

The NFLink™ module is placed on the plastic enclosure using two dedicated positioning holes and removed after configuration.

What is the maximum field current the regulator can handle?

The regulator supports a continuous field current up to 5 A and a short‑circuit current up to 10 A for a maximum of 10 seconds.

How can a too‑slow speed regulation loop be corrected?

Reduce the soft recovery parameter (%/s) in the configuration to speed up the regulation loop.