LABOM Ci4 Transmitter SIL Instructions Datasheet

Safety-related instructions and technical data for the LABOM Ci4 transmitter series, including SIL2 parameters, operating modes, failure rates, and…


LABOM Ci4 Transmitter SIL Instructions Datasheet - cover page
Brand
Labom
Document type
Datasheet
Language
English
Pages
4
File format
PDF
File size
69 KB
Published
20 October, 2026
Updated
20 October, 2026
MD5 checksum
DC536DD35E01FEBD7B805671B6B35D70

About this manual

This document provides safety-related instructions and technical specifications for the PASCAL Ci4 Type series CI4xxx transmitters manufactured by LABOM. It details the device's Safety Integrity Level (SIL) capabilities according to IEC/EN 61508, specifically covering SIL2 requirements.

What's inside

  • General Information
  • Safe Function
  • Technical Data
  • Accuracy
  • Reaction Times
  • Start-up Behaviour
  • Troubleshooting
  • Requirements for the Operator
  • Unsafe Operating Conditions
  • Regular Inspections

Specifications

Safety Integrity LevelSIL2
Operating ModeLow and continuous demand mode
Architecture1oo1
Device TypeType B
Hardware Fault ToleranceHFT 0
Safe Failure Fraction (SFF)>90%
Failure rate for safe detected failures2,03∙10-7 1/h
Failure rate for safe undetected failures2,37∙10-7 1/h
Reaction time in event of request220 ms
Reaction time in event of fault detection100 ms

Frequently asked questions

What is the safe function of the device?

The safe function according to IEC/EN 61508 is the 4…20 mA current signal.

What happens during initialisation?

A current of < 3.6 mA (alarm current) is issued at the output until initialization completes.

How can an alarm current be deactivated?

An alarm current caused by critical malfunction can only be deactivated by a manual restart.

Download PDF (69 KB)