Konnad C2000-A2-SDXA000-AX1 RS485 16DI Remote I/O Module User Manual

User manual for the Konnad C2000-A2-SDXA000-AX1 RS485 remote I/O module: 16 dry-contact DI inputs, wiring, setup, Modbus RTU registers and service.


Konnad C2000-A2-SDXA000-AX1 RS485 16DI Remote I/O Module User Manual - cover page
Brand
KonNad
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
26
File format
PDF
File size
2 MB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
10858A2BC6893C1031D7E6CF393CB991

About this manual

This Chinese user manual from Shenzhen United Innovation Automatic Control System Co., Ltd. (www.konnad.com) covers the C2000-A2-SDXA000-AX1, an RS485 switch-quantity remote I/O module with 16 dry-contact DI inputs. It starts with a quick-start chapter that lists the accessories needed before use (a USB-to-RS485 converter, wiring, a 9~27VDC power supply and a Windows PC), shows how to wire the DI inputs, and explains how to install the KonNaD device setup tool, search for the device and set its parameters. The default serial parameters are 9600,None,8,1 with RS485 address 1, and the chapter describes testing the device by refreshing and reading the DI1~DI16 point values.

A hardware chapter gives the technical specifications, product appearance, indicator meanings (DIx, RXD, TXD, PWR, RUN), port assignments with recommended cable types, dimensions and mounting (locating holes or DIN rail). The product-function chapter explains DI collection types, DI pulse counting, filter parameters and DI automatic clearing, followed by software operation steps and a communication protocol chapter with a register list and example frames for reading DI status, reading DI filter parameters, and writing single or multiple DI filter parameters. The manual ends with the packing list and the product service and warranty terms. This manual is written in Chinese.

What's inside

  • Quick Start
  • Device Wiring
  • Software Setup and Device Debugging
  • Hardware Description and Technical Specifications
  • Indicators and Ports
  • DI Collection
  • DI Pulse Counting and Filter Parameters
  • Communication Protocol and Register List
  • Packing List
  • Product Service and Warranty

Specifications

DI channels16
DI interface typeDry contact
DI input modeLevel + pulse counting
Digital filter interval6 sampling cycles
Acquisition frequency1kHz
Serial interfaceRS485, 1 port, Phoenix terminal
Communication protocolModbus RTU
Input voltage9~27VDC
Current80mA @ 12VDC
Dimensions75*105*30mm
MountingLocating holes / DIN rail
Operating temperature-40℃ ~ 85℃
Storage temperature-60℃ ~ 125℃
Relative humidity5% ~ 95% RH, non-condensing

Frequently asked questions

What are the default serial parameters and RS485 address of the C2000-A2-SDXA000-AX1?

The device default serial parameters are 9600,None,8,1 and the default RS485 address is 1. When searching for the first time the address range can be set to 1-10.

What power supply does the module require?

It uses a 9~27VDC input over the VS+ and GND terminals, drawing 80mA at 12VDC.

How many DI inputs does the module have and what type are they?

It provides 16 DI channels on Phoenix terminals with dry-contact inputs, and the DI input mode supports level plus pulse counting.

What communication protocol does the module use?

It communicates over RS485 using the Modbus RTU protocol; the manual includes a register list and example frames.

How long is the product warranty?

The warranty period is 6 years for the cased product and 3 years for the uncased product; accessories are not covered.