Design and construction manual for Keipla fire-resistant double-layer pipe, MLIT-certified and rated by the Japan Fire Equipment Safety Center.
This Japanese design and construction manual covers the Keipla fire-resistant double-layer pipe (耐火二層管), a fire-rated piping product whose inner pipe is rigid PVC. According to the document, the pipe passed a 2-hour fire test at the Building Materials Testing Center and holds Ministry of Land, Infrastructure, Transport and Tourism certification as well as a performance rating from the Japan Fire Equipment Safety Center, and is approved as a fire compartment penetration method.
The manual gives safety warnings for design, installation and use, expansion joint standards and installation criteria, thermal expansion data and formulas for the inner PVC pipe, the installation workflow from material acceptance to testing, jointing work, penetration work at fire compartments, connection to fixtures and dissimilar pipes, repair methods, and maintenance and cleaning guidance. This manual is written in Japanese.
| Fire resistance | Passed 2-hour fire test |
|---|---|
| Linear expansion coefficient (PVC pipe) | 7×10⁻⁵/℃ |
| Young's modulus (inner pipe) | 2,942 N/mm² |
| Heat-resistant PVC pipe (HT) max service temperature | 90℃ |
| Continuous hot water limit | Do not flow hot water of 60℃ or above continuously |
It holds Ministry of Land, Infrastructure, Transport and Tourism certification and a performance rating from the Japan Fire Equipment Safety Center, and is approved as a fire compartment penetration method.
One per floor, installed directly above or near the pipe fitting; in shaft compartments without floor slabs, one every 4 m or less.
Heat-resistant pipe adhesive must be used for heat-resistant PVC pipe (HT); it cannot be used above its 90℃ maximum service temperature.
Thermal stress can break the PVC pipe joint at the socket of the fitting and cause leaks, so expansion joints must be installed according to the criteria.