This manual covers the operation, installation, and maintenance of InterApp Desponia and Desponia plus butterfly valves in accordance with EN 161.
This document serves as an official guide for the installation, operation, and maintenance of InterApp butterfly valve models Desponia® and Desponia® plus. It outlines compliance requirements such as EN 161, safety protocols for operators, and specific instructions regarding transport and storage to ensure proper functionality.
| Ambient temperature range | -20ºC up to +60ºC |
|---|---|
| Opening and closing time | Less than one second for all sizes between DN 50 and DN 250 |
| Valve Class | Class A |
The specific maximum allowable pressure (PS) varies by model and is indicated on the valve label.
According to EN 161, the input signal must be 0-20 mA; a 4 mA trip signal is not allowed.
For sizes DN 50 to 80, replace after 100,000 cycles; for DN 80 to 150, after 50,000 cycles.