Delta pages for the IBM 8562 Service Guide, covering power information, PSU cable retention clips, PDU power, and Remote Code Load updates.
This document is a delta publication, P/N 03GH503, for the IBM 8562 Service Guide (base publication GC28-7010-00). It lists replacement pages and additional information for levels -00a through -00d, dated 2020 and 2021, and states that the changes remain in effect for later editions unless specifically altered.
The included pages cover power information for machine type 8562: PDU power, system power problems, power system information, PSU cable retention clips, and color coding of UPIC cables. They also include Licensed Machine Code changes, Remote Code Load scheduling, and failed-status reference codes.
| PDU support | Model T02 and Model LT2: 2 or 4 PDUs; Model GT2: 4 PDUs |
|---|---|
| Power system | Dual-source redundant 2N power |
| Voltage ranges | Single-phase: 30/32A, 200-240V AC (Wye); 3-phase: 30A, 200-240V AC (Delta) or 30/32A, 380-415V AC (Wye) |
| CPC drawer PSU power | 2000 W |
| Support Element PSU power | 900 W |
| PCIe+ I/O drawer PSU power | 1400 W |
The IBM 8562 is powered by Power Distribution Unit (PDU) power. The power system is described as a dual-source redundant 2N power supply.
Model T02 and Model LT2 support 2 or 4 PDUs, while Model GT2 requires 4 PDUs.
The document lists single-phase 30/32A at 200-240V AC (Wye) and 3-phase 30A at 200-240V AC (Delta) or 30/32A at 380-415V AC (Wye). It notes that 480 V AC and HVDC are not supported.
Cable retention clips must be installed on all Power Supply Units (PSUs) within the system.