Product information for the Honsberg OMNI-VHZ gearwheel flow transmitter/switch: characteristics, technical data, installation, programming and ordering code.
The Honsberg OMNI-VHZ is a flow transmitter/switch that combines a gearwheel volumetric flow sensor with an OMNI electronic head. A pair of gearwheels is moved in proportion to the flow rate and the movement is sensed through the housing wall, so the measurement is largely independent of viscosity. The device is intended for viscous, fluid, self-lubricating media and for aqueous fluids such as soaps, pastes and emulsions with a non-abrasive character.
The electronic head has a backlit graphical LCD that shows measured values to four places with their unit, an analog output of 4..20 mA or 0..10 V and two programmable push-pull switching outputs that can be used as PNP or NPN. The stainless steel housing has a hardened mineral glass pane, and parameters are set with a removable magnetic programming ring. The document gives technical data, pressure resistance and weight tables, ranges, materials, dimensions, installation and programming instructions, simulation mode, factory reset and the ordering code.
| Nominal width | DN 8..25 |
|---|---|
| Process connection | G 1/4..G 1 |
| Metering ranges | 0.02..150 l/min |
| Measurement accuracy | ±3 % of the measured value |
| Repeatability | ±0.3 % |
| Medium temperature | -25..+80 °C, optionally -25..+120 °C |
| Ambient temperature | -20..+70 °C |
| Supply voltage | 18..30 V DC |
| Power consumption | < 1 W |
| Analog output | 4..20 mA / max. load 500 Ω or 0..10 V / min. load 1 kΩ |
| Switching output current | 100 mA max. |
| Ingress protection | IP 67 / (IP 68 when oil-filled) |
| Display | Backlit graphical LCD, 32 x 16 pixels, -20..+70 °C |
The document states it is suitable for viscous, fluid, self-lubricating media and for aqueous fluids such as soaps, pastes and emulsions with a non-abrasive character.
It has an analog output of 4..20 mA (max. load 500 Ω) or 0..10 V (min. load 1 kΩ), plus two push-pull switching outputs rated at 100 mA maximum.
After modifying configuration parameters, the factory settings can be reset at any time using Code 989.
No. The device can be installed anywhere in the pipework system; a run-in section is not required and the direction of flow may be freely chosen.