Honsberg OMNI-LC Level Transmitter / Switch

Honsberg OMNI-LC is a level sensor with magnetic float and reed switch chain, offering analog and switch outputs with backlit LCD display.


Honsberg OMNI-LC Level Transmitter / Switch - cover page
Brand
Honsberg
Document type
Product Leaflet
Language
English
Pages
3
File format
PDF
File size
384 KB
Published
15 November, 2026
Updated
15 November, 2026
MD5 checksum
2459C27778BD5EFDDC5CBA7C9EBB428F

About this manual

The OMNI-LC is a level sensor using a magnetized float to activate a reed switch chain, connected as a potentiometer. It provides analog output (0/4..20 mA or 0/2..10 V) and two switching outputs with red LED indication. The device features a backlit LCD display, adjustable units, and a rotatable housing for easy installation and programming. It is designed for industrial use with IP67 protection and operates in temperatures from -20°C to +70°C.

Installation is simple: screw the sensor into a threaded hole on the container, then rotate the housing to align the display. Programming is done via a ring with STEP and EDIT positions, allowing modification of switching points, hysteresis, units, and output ranges. A simulation mode (code 311) allows testing wiring during commissioning, and factory defaults can be reset with code 989.

What's inside

  • Level Sensor with Reed Chain
  • Analog Output (0/4..20 mA or 0/2..10 V)
  • Two Switching Outputs
  • Backlit LCD Display
  • Adjustable Units
  • Installation
  • Programming
  • Simulation Mode
  • Factory Reset
  • Technical Specifications

Specifications

Output TypeAnalog (0/4..20 mA or 0/2..10 V) + Two Switching Outputs
DisplayBacklit graphical LCD (32 x 16 pixels)
Operating Temperature-20°C to +70°C
Ingress ProtectionIP67
Supply Voltage18..30 V DC
Power Consumption< 1 W
HysteresisAdjustable, not smaller than division, position dependent on characteristics

Frequently asked questions

What is the output type of the OMNI-LC?

It provides analog output (0/4..20 mA or 0/2..10 V) and two switching outputs with transistor push-pull configuration.

How do you program the OMNI-LC?

Programming is done via a ring with STEP and EDIT positions; turning the ring to position 2 allows modification of parameters like switching points and hysteresis.

What is the simulation mode for?

It allows testing the wiring during commissioning by creating a programmable analog output value (0..26 mA) without modifying the process variable.

Download PDF (384 KB)