This manual covers the design, installation, wiring diagrams, specifications, and spare parts for the George Fischer EA 05 electrical actuator unit.
The document serves as an instruction manual for the George Fischer Electrical Actuator Unit Type EA 05. It provides comprehensive information regarding the design elements, including a spurwheel gear, electric motor, and limit positioning components. The guide outlines safety warnings, such as disconnecting from mains before work and noting that the actuator lacks a safety position during power failure.
| Nominal voltage | 24 V, 115 V or 230 V, 50–60 Hz |
|---|---|
| Rated performance | 35 VA |
| Protection class | IP 65 |
| Duty cycle | 35% at TA 25 °C |
| Nominal torque | 15 Nm |
| Operating time | 10 sec/90° /L50141 |
| Ambient temperature | 0° to +50 °C |
Switch S2 opens at the «open» position, and Switch S1 opens at the «closed» position.
No, if the customer receives a complete actuated valve from George Fischer, no further adjustments are necessary.