Installation guide for the Franklin Fueling Systems Defender Series below grade double wall spill container, covering preparation, installation, integrity…
This installation guide covers the Franklin Fueling Systems Defender Series below grade double wall spill container. It includes safety precautions, replacement parts, required equipment, torque specifications, and preparation for new and retrofit sites.
The guide also addresses electronic sensor preparation, installation steps, integrity testing, and maintenance and inspection recommendations.
| Riser pipe height below finished grade | 17-19 in (430-480 mm) |
|---|---|
| Container elevated grade above finished grade | 1.0 in (25.4 mm) |
| M/F 4x4 adapter installed height | 1.75 in (45 mm) |
| Spill container to UST riser pipe torque | 125-150 ft-lbs (170-203 N-m) |
| Drop tube riser clamp to spill container torque | 75-100 ft-lbs (102-136 N-m) |
| Minimum loose cable for electronic sensor models | 10 ft (3 m) |
| Retrofit excavation size | 24 in diameter by 24 in deep |
| Minimum concrete removal around existing container | 36 in square |
The specified torque is 125-150 ft-lbs (170-203 N-m).
The riser pipe top should be 17-19 in (430-480 mm) below finished grade.
At least 10 ft (3 m) of cable should be left loose inside the manyway.
Excavate a 24 in diameter by 24 in deep area around the riser pipe.