Franklin Fueling Systems Moormann ATG Interface Installation Guide

This guide provides step-by-step instructions for installing and retrofitting the Franklin Fueling Systems Moormann ATG interface, including safety warnings…


Franklin Fueling Systems Moormann ATG Interface Installation Guide - cover page
Brand
Franklin Fueling Systems
Document type
Installation Guide
Language
English
Pages
12
File format
PDF
File size
1.4 MB
Published
26 October, 2026
Updated
26 October, 2026
MD5 checksum
F74C654ED82BEAABBEBE94B073332450

About this manual

The document serves as an installation guide for the Franklin Fueling Systems (FFS) Moormann ATG interface, which electronically reads a Moormann mechanical tape gauge. It covers both new installations and retrofits, emphasizing strict adherence to safety protocols when working with volatile hydrocarbon liquids in hazardous environments.

Detailed procedures are provided for assembling the plumbing system, including installing inlet fittings on tank tops, threading elbows and nipples, and positioning the gauge housing. The guide specifies requirements for pipe materials (galvanized), thread sealants, and specific clearances relative to tank walls.

What's inside

  • Important Safety Messages
  • Introduction
  • New Moormann ATG Interface Installation
  • Moormann ATG Interface Retrofits
  • Figure A Assembly Diagram
  • Safety Grounding Requirements
  • Hazardous Location Classifications

Specifications

Operating Temperature Range32º F (0º C) to a maximum temperature of 125º F (47º C)
Maximum Conduit Run Length2500 feet
Ground Resistance Requirementless than 1 ohm

Frequently asked questions

What type of tools must be used during installation?

Only non-sparking tools should be used to prevent explosions or fires from sparks in hazardous environments.

What are the minimum temperature requirements for installing the controller?

The controller must be located in an environment with a minimum temperature of 32º F (0º C).

What is the maximum allowable length for the conduit run from the probe to the controller?

The conduit run must not exceed 2500 feet.

What resistance level is required when metering the ATG Safety Ground to ground?

You must verify that less than 1 ohm of resistance is present.