Franklin Electric installation, application, and maintenance manual for single-phase and three-phase 60 Hz submersible motors covering storage, startup…
This manual provides comprehensive guidance for the installation, application, and maintenance of Franklin Electric submersible motors, both single-phase and three-phase, 60 Hz. It covers storage conditions, maximum start frequencies, mounting positions, transformer capacity requirements, torque effects on piping, generator use, check valve installation, water temperature and flow considerations, well sealing, grounding practices, control box wiring, motor specifications, fuse sizing, overload protection, installation verification procedures, preliminary electrical tests, and troubleshooting for electronic protection devices.
The document includes detailed tables for maximum starts per day, transformer kVA sizing, and torque tightening values. It also addresses three-phase motor cable selection, phase converter use, reduced voltage starting, variable frequency drive operation, and booster pump systems. Maintenance procedures and troubleshooting flowcharts for Pumptec, QD Pumptec, Subdrive/Monodrive, and Submonitor products are provided. This manual is written in Portuguese.
| Minimum run time for 4-inch motors after startup | 1 minute |
|---|---|
| Minimum torque per horsepower for threaded joints | 14 Nm per hp |
| Storage temperature lower limit | -40°C |
| Maximum storage duration at ≤37°C | 2 years |
At least 14 Nm per hp, so 70 Nm for a 5 hp motor.
Up to 2 years.
At least one minute to dissipate heat accumulated during startup.