Operation and configuration guide for the Fox Thermal Instruments FT3 data logger option, covering menu trees, setup and Modbus commands.
This manual describes the operation and configuration of the data logger option available on the Fox Thermal Instruments Model FT3 Thermal Gas Mass Flow Meter and Temperature Transmitter. The logger records interval totals based on the selected flow units at a customer-specified rate and keeps the most recent 31 records with a date and time stamp.
The document covers the front-panel menu trees, setup of the data logger, start/sync time and real time clock, viewing and clearing records, the Modbus commands that support reading and clearing the log, and a glossary of terms. It is marked 105774 Rev. B and applies to FT3 firmware version 3.09 and later.
| Records stored | 31 separate 24-hour daily totals with date and time stamp; oldest data overwritten |
|---|---|
| Recording interval | Customer selectable from 1 second to 1 month |
| Default start time | Midnight |
| Data access | RS485 Modbus and the Engineering Display |
| Manual revision compatibility | Rev B: FT3 firmware v 3.09 and later |
| Clear log Modbus register | Preset Register, Modbus Address 40213, data 0x57 |
It supports 31 records. When the number of samples exceeds 31, the old data is overwritten so only the most recent 31 records are kept.
Press the F1 and F4 keys at the same time. Use F2 to move to the next record, F1 to move back, and F4 to exit to normal mode.
The default is midnight (day, hour, minute and second all zero); only the hour, minute and second are used for the trigger.
Command 06 (Preset Register) at Modbus address 40213 with data 0x57 is used to clear all records in the log.