Fireye E100 burner management system with flame safeguard control, sequence operations, and safety shutdowns.
This document details the Fireye E100 burner management flame safeguard control system, including its hardware components and software sequence operations. The system provides automatic sequencing, flame proving, and lockout on flame failure. It includes a programmer, amplifier, and display module, with safety provisions for component failures and automatic recycling after power failure.
The system is UL Listed, FM Approved, and CSA Certified. It features an 8-character LED display for system messages, a wiring base for pre-wiring, and safety shutdowns within 4 seconds of flame failure. The control can be manually reset after any safety lockout, even after power failure.
| Flame Safeguard Control | Micro-processor Based |
|---|---|
| Sequence Control | Prepurge, Pilot Trial for Ignition (PTFI), Main Trial for Ignition (MTFI), Run, Postpurge |
| Display Module | 8-character LED Display |
| Messages Displayed | Minimum 42 different messages |
| Purge Period | Not less than 30 seconds |
| Post Purge | 15 seconds following shutdown |
| Control Model | Fireye E100 |
| Programmer Module | EP160 |
| Infrared Scanner | Fireye 48PT2 |
The control shall be the Fireye E100.
The control shall be Underwriters Laboratories Listed, Factory Mutual Approved, and Canadian Standards Associates Certified for its intended purposes.