Fireye 25SU3-2150 Rack-Mounted Flame-Safeguard Amplifier User Manual

Fireye 25SU3-2150 rack-mounted flame-safeguard amplifier manual covering installation, wiring, operation, programming, and specifications.


Fireye 25SU3-2150 Rack-Mounted Flame-Safeguard Amplifier User Manual - cover page
Brand
Fireye
Category
Other Electronics
Document type
User Manual
Language
English
Pages
28
File format
PDF
File size
1.1 MB
Published
20 November, 2026
Updated
20 November, 2026
MD5 checksum
24CF3725B19D861EB358B85F610315A8

About this manual

Fireye 25SU3-2150 is a rack-mounted flame-safeguard amplifier used to detect the presence or absence of a flame in single or multi-burner environments. It can receive pulse inputs from two flame scanners, A and B, and offers two logic programs with user-selectable operating parameters.

This document describes compatible scanners, ordering information, hardware, specifications, mounting racks, installation, front panel controls, operation, status and setpoint menus, password protection, programming examples, and electrical wiring diagrams.

What's inside

  • Description
  • Compatible Fireye Flame Scanners
  • Ordering Information
  • Specifications
  • Mounting Rack Specifications
  • Installation of Amplifiers and Power Supplies
  • Front Panel Layout and Description
  • Operation and Setpoints
  • Password Protection
  • Electrical Wiring Diagrams

Specifications

Height5.06 in (128.5 mm)
Depth8.0 in (203.2 mm)
Width (front panel)1.98 in (50.3 mm)
Self-check timingsOpen 3.5 sec; closed 0.5 sec
Signal inputsTwo flame scanner inputs
Analog output4-20 mA
Analog output load1000 ohms maximum
Flame relayDPDT Form C, one set fused contacts (RF1) 1.5 A
Alarm relaySPDT Form C
Contact ratings (minimum)40 mA resistive
Contact ratings (maximum)1 A resistive
Contact materialSilver cadmium oxide
Input voltage24 V AC (+10%, -15%) 50/60 Hz or 24 V DC (+/-10%)
Power consumption (one scanner)5 VA
Power consumption (two scanners)7.5 VA
Operating temperature-20 C to +60 C (-4 F to +140 F)
Storage temperature-20 C to +80 C (-4 F to +176 F)
Humidity0% to 85% RH non-condensing
Flame failure response time1 to 6 seconds, user-selectable
Flame relay delay on time0 to 10 seconds
Shipping weight1 lb (454 g)
MountingRack mount
KeypadFour membrane keys
DisplayEight-character alphanumeric LED
Safety approvalsFM, CE
Dynamic range1900 pulses per second
Power fuseOne replaceable 1.5 A fuse (F1); F2 not replaceable

Frequently asked questions

What input voltages does the 25SU3-2150 accept?

It accepts 24 V AC (+10%, -15%) at 50/60 Hz or 24 V DC (+/-10%).

How many flame scanners can the 25SU3-2150 use?

It can receive pulse inputs from two flame scanners, A and B.

What is the flame failure response time range?

The flame failure response time is adjustable from 1 to 6 seconds.

What is the dynamic range of the 25SU3-2150?

The dynamic range is 1900 pulses per second.