Fenwal AE90-FENIP65 Heat Detector Product Leaflet

Fenwal AE90-FENIP65 heat detector with thermal gradient compensation for fixed-temperature and rate-of-rise alarm detection.


Fenwal AE90-FENIP65 Heat Detector Product Leaflet - cover page
Brand
Fenwal
Category
Other Electronics
Document type
Product Leaflet
Language
Spanish
Pages
1
File format
PDF
File size
293 KB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
182359AE1982E39540FCEA74DA905C9A

About this manual

The Fenwal AE90-FENIP65 is a heat detector with thermal gradient compensation. It uses two connected chambers: an outer alloy chamber that expands quickly with ambient temperature and an inner chamber with a lower expansion coefficient containing electrical contacts.

A slow temperature rise expands both chambers equally and triggers the alarm at a set heat level, while a rapid rise activates the internal core and closes the alarm contact to trigger the alarm or release the agent. The sensor element is certified UL, FM and VdS, and the unit has an IP65 protection rating. This manual is written in Spanish.

What's inside

  • Descripción
  • Características técnicas
  • Certificaciones
  • Esquema de conexionado

Specifications

Protection ratingIP65
Relative humidity98%
Weight400 gr
Bimetal componentNilvia
Sensor materialSteel
Housing materialAluminum alloy
SupportStainless steel
Cable entries2x 3/4 UNI6125
Ground terminalsInternal - External
Temperature rise rate threshold4.4 °C/min

Frequently asked questions

How does the Fenwal AE90-FENIP65 heat detector work?

A slow temperature rise expands both chambers equally and triggers the alarm at a set heat level, while a rapid rise activates the internal core and closes the alarm contact.

What certifications does the temperature sensor element have?

The temperature sensor element is certified UL, FM and VdS.

What is the protection rating of the detector?

The detector has an IP65 protection rating.

What happens when temperature rises slower than 4.4°C per minute?

The outer chamber expands but not enough to trigger the alarm.

Download PDF (293 KB)