Fenwal 35-70 120 VAC DSI Ignition Control Conversion Guide

Provides safe gas ignition control and flame monitoring for 120 VAC gas burner systems


Fenwal 35-70 120 VAC DSI Ignition Control Conversion Guide - cover page
Brand
Fenwal
Document type
Other
Language
English
Pages
6
File format
PDF
File size
1.5 MB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
5AD5890E2874DD71E355BCED8365FB11

About this manual

This guide explains how to safely convert applications from the older Fenwal 05-14 analog controls to the newer 35-70 microprocessor-based ignition control. It covers terminal designations, wiring differences, grounding schemes, and agency approvals. The 35-70 offers improved flame sensitivity, LED diagnostics, polarity-insensitive wiring, and multiple lockout recovery methods. Key changes include the use of a B.GND terminal for burner grounding and the elimination of a manual reset button.

The guide also includes a cross-reference chart for popular control models and notes on specific wiring configurations, such as Single Spark and Sense versus Local Sense electrodes, and terminal orientation differences on the high voltage transformer.

What's inside

  • Conversion Guide 05-14 to 35-70
  • Terminal Designation and Size Comparison
  • Single Spark and Sense vs. Local Sense
  • Control Wiring Comparison
  • Footprint Comparisons
  • Agency Approval Comparisons
  • Cross Reference Chart

Specifications

Ignition Control Type120 VAC Direct Spark Ignition (DSI)
AccuracyIgnition and purge timings +/- 5%
Agency ApprovalsUL 372, UL 1998, CSA: ANSI Z21.2, FM (pending)

Frequently asked questions

What is the difference between Single Spark and Sense and Local Sense wiring?

Single Spark and Sense uses the high voltage wire to both supply spark energy and pass the flame sense current, eliminating the need for an additional sense wire. Local Sense requires a separate sense wire.

What does the 35-70 control replace?

The 35-70 replaces the 05-14, 05-13, and 05-38 controls.

What is the voltage rating for the 35-70 control?

The 35-70 is a 120 VAC control.

What is the new grounding terminal on the 35-70?

The B.GND terminal is used to ground the burner and complete the flame current signal circuit.

Download PDF (1.5 MB)

More Fenwal Manuals


View all Fenwal manuals →