Operation manual for the EW EW9L series three-phase intelligent energy meter, covering measurement, menu settings, alarms, communication and technical…
The EW9L series three-phase intelligent energy meter operation manual describes a meter for three-phase three-wire or three-phase four-wire systems with 28 measurement parameters, including voltage, current, active and reactive power, frequency and power factor. It covers panel indication, technical parameters, model variants, menu operation, system settings, communication parameters, alarms, tariff rates and time settings.
The meter supports four switch signal inputs and two switch signal outputs, true RMS measurement, programmable analog output, RS485 Modbus RTU communication, energy pulse output, alarm functions and power-failure memory. Optional functions include tariff statistics, demand statistics and harmonic analysis.
| Voltage input range | AC 3x57.7V / 3X220V; direct input L-N 0-600V, L-L 0-1000V |
|---|---|
| Voltage consumption | <1VA (each phase) |
| Current range | AC 0.025-5A |
| Current consumption | <0.4VA (each phase) |
| Voltage/current accuracy | 0.5 (RMS measurement) |
| Frequency | 30-500Hz, accuracy 0.1Hz |
| Power accuracy | Active/reactive/apparent power 0.5 |
| Energy accuracy | Active power 0.5, reactive power 1 |
| Power supply | AC/DC 100-240V (85-265V) |
| Dimensions | 96×96×104.6 mm |
| Communication | RS-485 Modbus-RTU |
| Pulse output | 2 energy pulse outputs, 9000imp/kwh |
| Digital inputs | 4 on/off inputs |
| Digital outputs | 2 on/off outputs, 250VAC/3A or 30V DC/5A |
| Analog output | 1 transformed analog output, 4-20mA DC, load <500Ω |
| Insulation resistance | >5MΩ |
Press the SET key for more than 5 seconds; if a user password is set, enter the correct password to access the user menu.
Input 1111 to clear energy.
Input 2222 to clear maximum demand.
Input 1234 to reset to factory setting.