Grounding connection specifications for the ERICO CADWELD exothermic welding system used for copper to copper and copper to steel electrical connections.
The ERICO CADWELD exothermic welding system is designed for creating permanent electrical grounding connections between copper to copper and copper to steel conductors. These connections are suitable for direct burial in earth or concrete and are designed to resist degradation over the lifetime of the grounding system.
The system complies with IEEE Standard 80 (IEEE Guide for Safety in AC Substation Grounding) and IEEE Standard 837 (Standard for Qualifying Permanent Connections Used in Substation Grounding). It includes a comprehensive numbering system for molds to identify connection types and conductor sizes.
| Compliance Standards | IEEE Standard 80 and IEEE Standard 837 |
|---|---|
| Recommended Conductor (Structures > 75 ft) | 2/0 AWG copper |
| Recommended Conductor (Structures < 75 ft) | #2 AWG copper |
| Bonding Conductor Size | #6 AWG copper |
The normal materials required are a mold, handle, weld metal, and packing material to prevent leaks.
They should be located away from areas of maximum tensile stress, such as near the free end of the bar in a lap splice.
Welding should not be harmful if the stresses in the rebar are below yield.