Installation instructions for ERICO INTERCEPTOR SI25i, SI40i and SI60i lightning protection terminals on a 5 m stainless steel cantilevered mast, including…
This ERICO instruction sheet shows an installation method for INTERCEPTOR SI25i, SI40i or SI60i terminals on a 5 m stainless steel cantilevered mast with an ER series terminal elevation 4 m above the structure. It includes mast, cable, strap, bonding clamp, downconductor and grounding system details.
The sheet also gives suggested grounding layouts, including three radial trenches per downconductor, conductor and ground rod sizes, and safety and responsibility notes for installation.
| Mast height | 5 m |
|---|---|
| Terminal elevation | 4 m above structure |
| Downconductors required | 2 |
| Radial grounding systems | 3 per downconductor |
| Trench depth | 1.5 ft (0.45 m) |
| Ground rod size | 5/8 in x 8 ft (16 mm x 2.4 m) |
| Ground rod depth below ground | 10 ft (3 m) |
| Crow's foot conductor size | Minimum 2/0 (50 mm2) |
| Mast support bracket spacing | 3.3 ft (1 m) |
Two downconductors are required.
Ground rods must extend 10FT [3M] below ground level.
The crow's foot requires a minimum 2/0 (50 mm2) conductor.
No. ERICO is not responsible for field installation of lightning protection systems.