User guide for Ecolink's WST-600 audio detector, designed to monitor smoke and CO alarms and transmit signals to control panels.
The WST-600 Audio Detector is designed to listen for audio signals from smoke or carbon monoxide detectors. Once confirmed as an alarm, it transmits a signal to a compatible 433MHz DSC security system. The device requires a 3Vdc lithium CR123A battery and has a 4-year lifespan. Installation must be within 6 inches of the detector for optimal performance. The manual covers enrollment, mounting, testing, and battery replacement procedures.
The device supports two zone types for smoke detection (88 or 87) and one for CO detection (81). It can be programmed in different modes, including generic listening mode, and includes safety warnings for proper installation and testing.
| Frequency | 433.92 MHz |
|---|---|
| Operating Temperature | 32°-120°F (0°-49°C) |
| Battery | One 3Vdc lithium CR123A (1550 mAh) |
| Battery Life | 4 years |
| Detection Distance | 6 in max |
It operates at 433.92 MHz.
Enter the 6-digit serial number printed on the back of the device. Use zone type 88 for smoke or 87 for delayed smoke, and 81 for CO. Set the wireless bit (bit 8) for the zone.
The maximum detection distance is 6 inches.
The battery lasts up to 4 years.