EA-ELEKTRO-AUTOMATIK UPS 712-21B Uninterruptible DC Power Supply User Manual

German/English user manual for the EA-ELEKTRO-AUTOMATIK UPS 712-21B uninterruptible 12V/21A DC power supply: installation, operation, alarms and technical data.


EA-ELEKTRO-AUTOMATIK UPS 712-21B Uninterruptible DC Power Supply User Manual - cover page
Brand
EA-ELEKTRO-AUTOMATIK
Category
Power Management
Document type
User Manual
Language
German
Pages
4
File format
PDF
File size
27 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
23B7E07C4EC3ECFD392ED04D10E6FB5E

About this manual

This is the operating manual (Bedienungsanleitung) for the EA-ELEKTRO-AUTOMATIK UPS 712-21B uninterruptible DC power supply, article number 18 175 202. The German text is followed by an English translation, and the document closes with a parts list and a circuit diagram for the unit.

The manual describes the power supply/charging unit with an external maintenance-free lead battery, how the load is fed without interruption when the mains fails, the "Output On/Off" push-buttons, the "Automatic RESET" DIP switch and the two isolated alarm contacts, together with safety notes, installation instructions and the technical data table. This manual is written in German.

What's inside

  • Allgemeines / Safety notes
  • Technische Beschreibung / Technical description
  • Installation
  • Inbetriebnahme / Operation
  • Automatic RESET DIP switch
  • Alarm relay contacts
  • Technische Daten / Technical Data
  • Stückliste / Partlist
  • Stromlaufplan / Circuit diagram

Specifications

Input voltage88...264V / 47...63Hz
Output voltage10...13,5V
Output current21A
Efficiency total>83%
Voltage regulation during mains operation+0,5%
Ripple<150mV pp
Back-up time at 12A with 6,5Ah batteryca. 15 Minutes
Rated battery voltage12V
Operating temperature0 … 50°C
Storage temperature-30...70°C
Weight2,3kg
Dimensions (W x H x D)240 x 133 x 87 mm
Max. current per output terminal11A
Alarm contact capacity60V/1A

Frequently asked questions

What happens to the load if the mains supply fails?

The battery supplies the load without any interruption; the batteries are connected in parallel to the output.

At what battery capacity does the unit switch the output off?

The output is shut down at a battery capacity of approximately 20% to protect the batteries from deep discharge.

What do the two alarm contacts report?

One contact signals "Charging voltage LOW" below 12,5V and the other signals "Battery voltage LOW" below 11,5V, with a contact capacity of 60V/1A.

Can the output come back automatically after the mains returns?

Yes, if the "Automatic RESET" DIP switch, factory set to "0", is set to "I", the output voltage is available immediately after mains return.

Download PDF (27 KB)