DEHN VCSD 40 IP65 / EXFS 100 Oil and Gas Pipeline Cathodic Protection Lightning Protection Product Leaflet

DEHN leaflet on lightning and surge protection for oil and gas pipelines with cathodic protection, covering VCSD 40 IP65 and EXFS 100.


DEHN VCSD 40 IP65 / EXFS 100 Oil and Gas Pipeline Cathodic Protection Lightning Protection Product Leaflet - cover page
Brand
dehn
Category
Other
Document type
Product Leaflet
Language
Chinese
Pages
16
File format
PDF
File size
1.8 MB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
535AD9D020CF23580CB5D0F9791A74EC

About this manual

The DEHN document presents a lightning and surge protection solution for oil and gas pipelines that use cathodic protection. It explains how interference from traction systems, high-voltage lines, earth faults and lightning can produce transient, temporary and long-time overvoltages, and how the protection scheme is intended to limit these below defined values and reduce damage to insulating flanges, cathodic protection systems and field instruments.

The document covers products including the VCSD 40 IP65 intelligent decoupling device, EXFS 100 / EXFS 100 KU insulating spark gaps, the NAK SN4631 EXFS coaxial junction box, DEHNpipe MD Ex (i) and CD Ex (i), BLITZDUCTOR XT and BLITZDUCTOR XT Ex (i), the DRC MCM XT status monitoring system, DEHNventil modular and the DEHN HVI high-voltage isolating lightning protection system. This manual is written in Chinese.

What's inside

  • Protection of oil and gas pipelines against overvoltage interference
  • Overvoltage interference on oil and gas pipelines
  • Cathodic protection system
  • Intelligent decoupling device VCSD 40 IP65
  • VCSD 40 IP65 time suppression characteristics
  • Rectifier protection
  • EXFS 100 / EXFS 100 KU insulating spark gap and NAK SN4631 coaxial junction box
  • Field instrument protection
  • DEHNpipe MD Ex (i) and BLITZDUCTOR XT
  • DEHNventil modular, DRC MCM XT and DEHN HVI high-voltage isolating system

Specifications

VCSD 40 IP65 response thresholdAdjustable, AC 3 V to 50 V
VCSD 40 IP65 transient suppression voltage< 1.25 kV within 1 ms
VCSD 40 IP65 temporary suppression voltage< 940 V from 1 ms to 200 ms
VCSD 40 IP65 long-time suppression voltageAC 3 V to 50 V, adjustable (> 200 ms)
EXFS 100 discharge capability100 kA (10/350 µs) and 100 kA (8/20 µs)
EXFS 100 current carrying capacity500 Arms / 0.2 s
DEHNpipe MD Ex (i) nominal voltage24 V d.c.
DEHNpipe MD Ex (i) mountingM20 x 1.5 or 1/2 14 NPT thread

Frequently asked questions

What types of overvoltage can the VCSD 40 IP65 suppress?

The VCSD 40 IP65 can suppress long-time, temporary and transient overvoltages.

What is the response threshold of the VCSD 40 IP65?

It is adjustable from AC 3 V to 50 V.

What discharge capability does the EXFS 100 insulating spark gap have?

It has a discharge capability of 100 kA (10/350 µs) and 100 kA (8/20 µs).

What is the nominal voltage of the DEHNpipe MD Ex (i)?

The nominal voltage is 24 V d.c.