Continental Control Systems CTL-1250 Current Transformer Spec Sheet

Continental Control Systems CTL-1250 split-core current transformers provide IEEE C57.13 class 0.6 accuracy for revenue-grade energy management metering.


Continental Control Systems CTL-1250 Current Transformer Spec Sheet - cover page
Brand
CONTINENTAL CONTROL SYSTEMS
Category
Current Monitor
Document type
Product Leaflet
Language
English
Pages
1
File format
PDF
File size
196 KB
Published
22 November, 2026
Updated
22 November, 2026
MD5 checksum
E18A83A26A21005C7E1100053A061D27

About this manual

The CTL Series split-core current transformers from Continental Control Systems provide IEEE C57.13 class 0.6 accuracy and are UL listed for energy management equipment. They are rated for 250 or 400 Amps primary current at 600 Vac, 60 Hz.

Output is 333.33 mVac at rated current, with an integral burden resistor and no shorting block needed. Standard lead length is 8 ft (2.4 m) of 18 AWG wire, and the units are assembled in the USA.

What's inside

  • Specifications
  • Accuracy
  • Phase angle
  • Models
  • Dimensions
  • Approvals
  • Operating temperature

Specifications

Accuracy±0.50% from 15% to 100% of rated primary current
Phase angle error±0.25 degrees (15 minutes) from 50% to 100% of rated current
Primary rating250 or 400 Amps, 600 Vac, 60 Hz nominal
Output333.33 mVac at rated current
Operating temperature-30°C to 55°C
Standard lead length8 ft (2.4 m), 18 AWG
Accuracy standardsIEEE C57.13 class 0.6, IEC 60044-1 class 0.5S

Frequently asked questions

What is the output at rated current?

The output is 333.33 mVac at rated current.

What primary current ratings are available?

The transformers are rated for 250 or 400 Amps primary current.

Is a shorting block required?

No, the units have an integral burden resistor and no shorting block is needed.

What is the standard lead length?

Standard leads are 8 ft (2.4 m) of 18 AWG wire.