Installation and operation manual for the Condair MLBU adiabatic humidification boosting unit, covering safety, hygiene, installation, commissioning…
The Condair MLBU is an adiabatic humidification boosting unit intended for adiabatic humidification cooling and process water. This installation and operation manual is intended for engineers and properly trained technical personnel and covers safe use, performance, and longevity of the equipment.
The manual addresses health and safety, hygiene and Legionella prevention, intended use, warranty, delivery and storage, inlet water quality requirements, product overview, installation, commissioning, operation, maintenance, troubleshooting, and product data.
| Inlet water conductivity | 0.2 -1000 µS/cm |
|---|---|
| Inlet water silt index | Max. 3 |
| Inlet water potassium permanganate | Max. 10 mg/l |
| Inlet water turbidity | Max. 1 |
| Inlet water temperature | Max. 15°C |
| Inlet water iron | Max. 0.2 mg/l |
| Inlet water manganese | Max. 0.05 mg/l |
| Inlet water hardness | Max. 20º dH |
| Inlet water free chlorine | Max. 0.1 mg/l |
The MLBU is intended as a boosting unit for adiabatic humidification cooling and process water.
Condair recommends connecting the MLBU system to a clean, potable mains water supply of drinking water quality.
MLBU parts are covered by a two-year warranty from the invoice date, except for replacement parts listed in the routine maintenance section.
Condair recommends adding SANOSIL S010 AG 5% to the tank at a desired concentration of 0.1%.