Condair CH3-D Evaporative Humidifier Technical Manual

This manual covers the technical specifications, installation, operation, and maintenance of the Condair CH3-D direct-drain wet membrane humidifier.


Condair CH3-D Evaporative Humidifier Technical Manual - cover page
Brand
Condair
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
36
File format
PDF
File size
974 KB
Published
21 October, 2026
Updated
21 October, 2026
MD5 checksum
DDBBFB1E350C7D9192A98CCF3CFC40AC

About this manual

The document is a technical manual for the Condair CH3-D series, which is a direct-drain (one-pass) evaporative humidification system. It details the product's composition, including the stainless steel frame, wet membrane body, and water distribution system.

The guide provides comprehensive instructions on design selection based on specific parameters like saturation efficiency and air resistance, installation procedures for electrical and hydraulic components, operational guidelines, and maintenance tasks such as descaling and troubleshooting common faults. This manual is written in Chinese.

What's inside

  • Introduction
  • Safety Precautions
  • Product Overview
  • Composition of the Humidifier
  • Design Selection
  • Operating Conditions
  • Installation Instructions
  • Operation
  • Maintenance and Troubleshooting

Specifications

Wet membrane thickness (CH3-D-50)50 mm
Water pressure requirement0.1~0.8 Mpa

Frequently asked questions

What is the standard test condition for humidification capacity?

The standard test conditions are a dry bulb temperature of 40℃, relative humidity of 15%, and face velocity of 2.5m/s.

How should scale buildup on the wet membrane be cleaned?

Use a descaling agent to clean the wet membrane surface to restore its water absorption performance and humidification effect.

What causes the humidifier light to be on but the wet membrane to remain dry?

Possible causes include a closed water flow adjustment ball valve, lack of water source, incorrect wiring or failure of the solenoid valve, or clogged spray holes.