Installation and operation guide for Bradford White's Laars Heating Systems VW series volume water heaters, sizes 2000-5000 liters.
This manual provides step-by-step instructions for installing and operating the Laars Heating Systems VW series volume water heaters. It covers general information, installation requirements, combustion air, venting, gas and electrical connections, water piping, and maintenance. Safety warnings emphasize that only qualified technicians should install or service the unit to prevent carbon monoxide risks and void the warranty.
The manual includes sections on indoor and outdoor installation, troubleshooting, parts lists, and conversion between indoor and outdoor models. It also addresses water chemistry and potential damage from scaling or corrosion, advising on corrective actions like replacing pump impellers or using cupronickel tubes. This manual is written in Chinese.
It must be installed and serviced by a professional service technician qualified in hot water heater installation and maintenance. Installation and service must also be performed by a qualified installer, service agency, or gas supplier.
All low volume hot water heaters must have continuous flow through the heat exchanger when firing. The system pump must develop enough pressure to overcome the resistance of the heater and the entire circulating system at the designed flow rate.
For both indoor and outdoor heaters, the required clearance is 24 inches at the top, 24 inches at the water connection side, 24 inches at the opposite side, 48 inches at the front, 24 inches at the rear, and 6 inches at the vent.
Heaters must be installed on non-combustible flooring and must never be installed on carpeting. The base must extend at least 12 inches on all sides of the heater frame and can use concrete blocks or tile at least 7 inches high with 3-inch minimum air openings.