BHEL 650kVA Transformer Technical Specifications

Technical specifications for a BHEL 650kVA outdoor oil-immersion 3-phase transformer used in a 1MWh Battery Energy Storage System.


BHEL 650kVA Transformer Technical Specifications - cover page
Brand
BHEL
Category
transformer
Document type
Product Leaflet
Language
English
Pages
3
File format
PDF
File size
264 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
038F47C3C449A4FA7E5F6B7FF53E40E0

About this manual

This document details the technical requirements for a 650 kVA, 3-phase, 2-winding transformer designed for a 1MWh Battery Energy Storage System. The transformer is an outdoor, oil-immersion type with ONAN cooling, intended to step up non-sinusoidal inverter output from 415 V (LV side) to 6.6 kV (HV side).

It specifies construction standards according to IS: 2026, including the use of electrolytic grade copper for windings and CRGOS silicon steel for the core. The document also outlines the required accessories, painting specifications, and the inspection and testing protocols the vendor must follow.

What's inside

  • Introduction
  • Scope for the Vendor
  • Technical Specifications
  • Painting
  • Constructional features
  • Fittings and accessories
  • Inspection and testing of transformer at vendor works
  • Documents to be submitted

Specifications

Rating650 kVA
Voltage (HV/LV)6.6 kV / 415 V
Cooling TypeONAN
Frequency50 Hz, +/- 3%
Vector GroupDyn11
IP ClassIP55
EfficiencyMinimum 98.5% at full load (100%)
Percentage Impedance< 6 %

Frequently asked questions

What are the tap provisions for the HV winding?

The HV winding features an off-circuit tap switch with five positions: +5%, +2.5%, 0, -2.5%, and -5%.

What is the purpose of the 650 kVA transformer?

It is used to step up the non sinusoidal output of an inverter from 415 V on the LV side to a 6.6 kV HV level.

What is the IP class rating for the transformer and its boxes?

The transformer, including the marshalling and cable boxes, shall be of IP55.

What material is used for the HV and LV windings?

Both the HV and LV windings are made of electrolytic grade copper.