Belimo Energy Valve 272031/272046 Product Leaflet

Technical data for Belimo Energy Valve 272031 and 272046, including flow control, temperature measurement, power supply, and installation notes.


Belimo Energy Valve 272031/272046 Product Leaflet - cover page
Brand
Belimo
Category
Industrial Robot
Document type
Product Leaflet
Language
English
Pages
3
File format
PDF
File size
720 KB
Published
02 November, 2026
Updated
02 November, 2026
MD5 checksum
1EE7E5AA15709EE771B66301091941B2

About this manual

The Belimo Energy Valve 272031 and 272046 are energy metering, pressure-independent control valves for water-side HVAC applications. They measure flow and temperature using built-in sensors and control power via Power Control logic to optimize performance regardless of pressure or temperature variations. The valves support communication protocols including BACnet IP, BACnet MS/TP, Modbus RTU/IP, and web server access. They are designed for chilled or hot water systems with up to 60% glycol, and feature stainless steel ball and stem, nickel-plated brass body, and EPDM packing. Installation includes wiring diagrams and safety warnings for live electrical components.

What's inside

  • Technical Data
  • Flow Control
  • Temperature Measurement
  • Power Supply
  • Communication Protocols
  • Installation Notes
  • Wiring Diagrams

Specifications

Flow Characteristicequal percentage or linear
GPM Range1.65 - 5.5
Valve Size0.5 “ [15]
Media Temperature Range (Water)14°F to 250°F [-10°C to 120°C]
Power Supply24 VAC, ±20%, 50/60 Hz, 24 VDC, ±10%
Operating Range2 to 10 VDC (default)
Housing ProtectionIP40, NEMA 1, UL
Weight (272031)4.9 lb [2.2 kg]
Weight (272046)1.5 lb [0.7 kg]
Communication ProtocolsBACnet IP, BACnet MS/TP, Modbus RTU, Modbus IP, web server, Belimo MP-Bus

Frequently asked questions

What is the flow measurement tolerance for the Energy Valve?

Flow Measurement Tolerance ±2%* at 68°F (20°C) & water.

What communication protocols does the Energy Valve support?

BACnet IP, BACnet MS/TP, Modbus RTU, Modbus IP, web server, Belimo MP-Bus.

What is the operating temperature range for the 272046 model?

Ambient Temperature Range -22°F to 122°F [-30°C to 50°C].

What is the power consumption of the valve when running?

Power Consumption Running 4 W.