Belimo Energy Valve V3.2 Technical Databook

Technical datasheet for the Belimo Energy Valve V3.2, a pressure-independent control valve for HVAC systems that measures flow and calculates energy…


Belimo Energy Valve V3.2 Technical Databook - cover page
Brand
Belimo
Category
Other
Document type
Datasheet
Language
English
Pages
24
File format
PDF
File size
5.5 MB
Published
13 October, 2026
Updated
13 October, 2026
MD5 checksum
15C42491DE2AE1F657334116244A9547

About this manual

This document is a technical databook for the Belimo Energy Valve™ V3.2 Control Valve Range. It covers two main product series: the internal thread version (EV..R+BAC) and the PN16 flange version (P6..W..EV-BAC). The valves are designed for modulating water-side control in air handling and heating systems, featuring sensor-operated flow rate or power control with integrated web servers for communication via BACnet IP, BACnet MS/TP, or Belimo MP-Bus.

What's inside

  • Product Overview
  • Technical Data
  • Electrical Data
  • Functional Data
  • Safety Notes
  • Mounting Instructions
  • Materials
  • Ordering Sample

Specifications

Nominal VoltageAC/DC 24V
Communication ProtocolsBACnet IP, BACnet MS/TP, Belimo MP-Bus
Measuring Principle (Internal Thread)Ultrasonic volumetric flow measurement
Measuring Principle (Flange)Magnetic inductive volumetric flow measurement
Measuring Accuracy±2% (of 25...100% nom)
Pressure RatingPN16
Media Temperature Range-10°C...120°C
Ambient Temperature-30...50°C
Degree of ProtectionIP54

Frequently asked questions

What communication protocols does the Energy Valve support?

The valve supports BACnet IP, BACnet MS/TP, Belimo MP-Bus, or conventional control.

Can the valve be used with glycol solutions?

Yes, it can handle water with glycol up to a maximum of 60% volume.