Beckwith Electric M-6200A Digital Regulator Control installation guide covering dimensions, connections, and replacement of Cooper regulator controls.
This Application Guide provides installation instructions for the Beckwith Electric M-6200A Digital Regulator Control and the B-2355 Series Cooper Hardware Kit. It covers mechanical orientation, physical dimensions, external connections, and procedures for replacing Cooper CL-2, CL-2A, CL-4A, CL-4B, CL-4C, CL-5, and CL-6 regulator controls.
The guide also includes terminal block assignments, torque requirements, grounding information, control power backup connections, and instructions for installing TapTalk S-6200 communications software and establishing initial local communications via USB.
| Voltage Withstand | 140 V continuous |
|---|---|
| Load Current | 0.48 amps continuous |
| Output Raise and Lower Circuits | 6 amps AC |
| Alarm Contacts AC Rating | 6.0 amps AC, 125 V |
The M-6200A directly replaces Cooper CL-2, CL-2A, CL-4A, CL-4B, CL-4C, CL-5, and CL-6 regulator controls.
TapTalk S-6200 Communications Software is installed for initial local communications.
Always disconnect power and discharge circuits before working on the unit.