This manual covers the B&R X20BC008U OPC UA Bus Controller, including technical specifications, LED status indicators, network configuration, and Ethernet…
This document serves as the user manual for the B&R X20BC008U OPC UA Bus Controller, Version 1.10. It provides general information about the OPC Unified Architecture (OPC UA) protocol and the controller's role in industrial communication between end devices. The manual details the technical description, including order data, technical specifications, and required accessories such as the X20 bus base and power supply modules.
| Transfer rate | 100 Mbit/s |
|---|---|
| Physical layer | 100BASE-TX |
| Line length | Max. 100 m |
| Power consumption | 2.5 W |
| Minimum cycle time (Fieldbus) | 10 ms |
| Minimum cycle time (X2X Link) | 2 ms |
| Operating temperature (Horizontal) | -25 to 60°C |
| Degree of protection | IP20 |
The default IP address is 192.168.1.1.
The hostname is composed of 'br' + 'opc' + the address switch value (e.g., bropc215).
The default OPC UA server port is 4840.