ATTACK DPX Wood Gasifying Boiler User Manual

ATTACK DPX wood gasifying boiler manual covering installation, operation, maintenance, technical parameters and safety.


ATTACK DPX Wood Gasifying Boiler User Manual - cover page
Brand
ATTACK
Category
Heater
Document type
User Manual
Language
English
Pages
51
File format
PDF
File size
1.6 MB
Published
15 November, 2026
Updated
15 November, 2026
MD5 checksum
9B56F057D2D08C56573220C735F60B4B

About this manual

The ATTACK DPX is a wood gasifying boiler available in Standard, Profi and Lambda versions with nominal outputs from 15 to 45 kW. The manual covers technical parameters, dimensions, instrument panels, installation, operation, maintenance, safety and troubleshooting.

It specifies dry wood fuel with 12-20% humidity, a minimum return water temperature of 65°C, and an operating water temperature of 80-90°C.

What's inside

  • Introduction, general description
  • Technical parameters
  • Boiler dimensions
  • Instrument panel of ATTACK DPX STANDARD, PROFI LAMBDA
  • Purpose of usage, technical description, description of the STANDARD version
  • Technical description of DPX PROFI
  • Technical description of ATTACK DPX LAMBDA
  • Assembly and installation of boiler
  • Maintenance of the heating system, fuel
  • Possible faults and methods of their removal

Specifications

Nominal output15, 25, 30, 35, 40, 45 kW
Maximum operating pressure250 kPa
Water volume80, 100, 110, 128 l
Electrical connection230 V/50 Hz/10 A
FuelDry wood, 15-17 MJ/kg, 12-20% humidity, 80-150 mm diameter
Boiler efficiency89, 89, 89, 89, 90, 90 %
Flue gas connection diameter150 mm
Boiler height1240 mm
Boiler width700 mm
Boiler depth840, 1240, 1340, 1340, 1440, 1440 mm
Minimum return water temperature65°C
Operating water temperature80-90°C
Prescribed chimney draught23 Pa

Frequently asked questions

What fuel is prescribed for the ATTACK DPX boiler?

Dry wood with a heat value of 15-17 MJ/kg, humidity of 12-20%, and diameter of 80-150 mm.

What return water temperature must be maintained?

The return water temperature into the boiler must be at least 65°C.

What is the prescribed operating water temperature?

The water temperature in the boiler should be 80-90°C.

What should be done after disconnecting an operating boiler from electricity?

Burning continues in attenuation regime, and the boiler door must not be opened until the temperature is below 40°C.