Engineering manual for the Ascon Tecnologic A30 converter covering dimensions, connections, installation, serial interfaces, power supply, specifications…
The Ascon Tecnologic A30 is a converter between USB, RS-232, RS-485, and TTL interfaces, available in A30U and A30- models. This engineering manual covers outline dimensions, the connection diagram, installation and mounting requirements, preliminary hardware settings, serial interface and power supply details, technical characteristics, and ordering information.
The document also states operating conditions, isolation and EMC compliance details, a 12-month warranty, maintenance guidance, and cleaning instructions.
| Case material and flammability | Plastic, self-extinguishing degree V-0 according to UL 94 |
|---|---|
| Terminals protection | IP 20 according to EN 60070-1 |
| Terminal block (power supply) | Screw terminals, screw M3, cables 0.25...2.5 mm² (AWG 23 to AWG 14) |
| Terminal block (RS-232/RS-485) | Screw terminals, screw M2, cables 0.25...1.5 mm² (AWG 23 to AWG 16) |
| Dimensions | 28 x 88 mm, depth 78 mm |
| Weight | 180 g approx. |
| Power supply (100/240 V option) | 100...240 VAC (-15...+10%) |
| Power supply (24 V option) | 24 VAC/DC (±10%) |
| Power consumption | 5 VA max. |
| Isolation (100/240 VAC supply to communication lines) | Reinforced according to EN 61010-1; voltage test 2500 Vrms (1 min) |
| Isolation (24 VAC/DC supply to communication lines) | Reinforced according to EN 61010-1; voltage test 1500 Vrms (1 min) |
| Isolation (master to slave side) | Functional isolation (250 VAC) |
| Operating temperature | 0...50°C (32...122°F) |
| Storage temperature | -30...+70°C (-22...+158°F) |
| Humidity | 20...85% RH, non condensing |
| USB compatibility | 2.0 full speed compliant with USB 1.1 |
| Maximum baud rate (RS-485 only) | 38400 baud |
| RS-485 connections | Up to 30 devices to one remote master unit |
| Maximum cable length | 1500 m at 9600 baud |
| Electromagnetic compatibility | Compliance with directive EMC EN 61326-1 and directive LV EN 61010-1 |
| Installation category | II |
| Pollution category | 2 |
| Warranty period | 12 months from delivery date |
38400 baud.
Up to 30 devices; an isolation unit (RS485 to RS485) is required when other units must be connected.
1500 m at 9600 baud.
No; provide a T type 1A, 250 V fuse externally.