Amiad 2-Inch Manual Steel Filter 910101-00057 Installation and Maintenance Instructions

Amiad 2-inch manual steel filter 910101-00057 installation and maintenance instructions covering safety, installation, cleaning, and parts.


Amiad 2-Inch Manual Steel Filter 910101-00057 Installation and Maintenance Instructions - cover page
Brand
amiad
Category
Other
Document type
Installation Guide
Language
English
Pages
6
File format
PDF
File size
744 KB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
2EF8BE3F879130C7AA0968AA533A527E

About this manual

This document provides installation and maintenance instructions for the Amiad 2-inch Manual Steel Filter, catalog number 910101-00057, dated January 2017. It includes safety instructions, principle of operation, installation site recommendations and instructions, cleaning steps, a typical installation drawing, and a parts schedule and drawing.

According to the text, water flows through a stainless steel filtration element from the inside out, and the filter has to be cleaned manually. Cleaning is required when the pressure drop between pressure checkpoints exceeds 0.7–1.0 bar (10–15 psi), or when downstream pressure or flow becomes unacceptably low. The manual also warns not to loosen the filter lid bolts until pressure has been released.

What's inside

  • Safety Instructions
  • Use of Lifting Equipment
  • Principle of Operation
  • Installation Site Design Recommendations
  • Installation Instructions
  • Typical Installation
  • Cleaning the Filter
  • Parts Schedule
  • Parts Drawing

Specifications

Cleaning pressure drop threshold0.7–1.0 bar (10–15 psi)
Molded weavewire screenS/ST316L, 500 sq.cm, 130 micron, Amiad 2"
Perforated screenS/ST316L, 500 sq.cm, 1500 micron, Amiad 2"

Frequently asked questions

When should the filter element be cleaned?

Clean it when the pressure drop between pressure checkpoints exceeds 0.7–1.0 bar (10–15 psi), or when downstream pressure or flow becomes unacceptably low.

How does water flow through the filter element?

Water flows through the filter element from the inside out, so dirt and debris accumulate on the inside surface.

What must be done before loosening the filter lid bolts?

Pressure must be released first; the manual warns not to loosen the filter lid bolts until pressure has been released.

How is the filter element cleaned?

Remove the filter element and clean it by spraying a hard stream of water on its outside surface; stubborn dirt may be removed with a light to medium stiffness brush.