ABB S200 Series MCB Torque Setting Guide

A reference guide listing recommended tightening torque values for ABB S200 Series MCBs and various other electrical components.


ABB S200 Series MCB Torque Setting Guide - cover page
Brand
ABB
Category
Other Electronics
Document type
Product Leaflet
Language
English
Pages
6
File format
PDF
File size
275 KB
Published
21 November, 2026
Updated
21 November, 2026
MD5 checksum
2712C7A57BC169E6BA4CD054168BAE5D

About this manual

This document provides specific torque settings for the installation and maintenance of ABB S200 Series Miniature Circuit Breakers (MCBs) and other related devices. It specifies the required Newton-meter (Nm) values for different connection types, such as main connections, coil terminals, and auxiliary contacts, to ensure proper electrical safety and mechanical integrity.

What's inside

  • S200 Series MCB
  • S280 Series MCB
  • S800 Series MCB
  • F200 Series RCCB
  • DDA Addon Block
  • DS201/DS202C RCBO
  • E200 Series Switches
  • Installation Contactors
  • Thermal Overloads
  • MCCB Torque Settings

Specifications

S200 Series MCB Torque2.8 Nm
S280 Series MCB Torque2.5 Nm
S800 Series MCB Torque3.0 - 4.0Nm (max)
F200 Series RCCB (up to 100A) Torque2.8Nm
F200 Series RCCB (125A) Torque3Nm
DS201/DS202C RCBO Torque2.8Nm
DS271 Single module RCBO (top terminal) Torque2Nm
DS271 Single module RCBO (bottom terminal) Torque1.8Nm
T1 MCCB (70mm2 Cable conns) Torque7Nm
T2 MCCB (Front Bar Conns) Torque6Nm

Frequently asked questions

What is the torque setting for an S200 Series MCB?

The recommended torque setting is 2.8 Nm.

What is the maximum torque for an S800 Series MCB?

The maximum torque setting is 4.0 Nm.

What is the torque for the top terminal of a DS271 RCBO?

The torque for the top terminal is 2 Nm.