This guide provides instructions for the installation, wiring, and startup of the ABB ACS880-31 industrial drive.
This document serves as a quick installation and startup guide for the ABB Industrial Drive ACS880-31. It outlines essential safety precautions, site inspection requirements, and specific steps for mounting the drive on a wall. The guide covers necessary checks for the installation environment, including ventilation and material flammability, to ensure safe operation. This manual is written in Chinese.
| Mounting Torque (R3) | 1.7 N·m |
|---|
You must wait 5 minutes to allow the intermediate circuit capacitors to discharge.
You must use a measurement voltage of 1000 VDC.
The insulation resistance must exceed 100 Mohm.