Italian hardware manual for ABB ACS800-04/04M/U4 drive modules, covering safety, grounding, mechanical installation, PCB handling, and fiber optic cable…
ABB ACS800-04/04M/U4 Drive Modules Hardware Manual is an Italian-language document for ABB drive modules. It presents safety warnings, grounding requirements, mechanical installation and maintenance precautions, printed circuit board handling, and fiber optic cable handling.
The manual also lists related ABB hardware, firmware, and optional device manuals and guides, and identifies the ACS800-04/ACS800-04M modules for 45 to 560 kW and ACS800-U4 modules for 60 to 600 hp. This manual is written in Italian.
| Power range (ACS800-04/ACS800-04M) | 45 to 560 kW |
|---|---|
| Power range (ACS800-U4) | 60 to 600 hp |
| Minimum fiber optic cable bend radius | 35 mm (1.4 in) |
| Recommended protective earth conductor | at least 10 mm2 copper or 16 mm2 aluminum |
ACS800-04 and ACS800-04M modules cover 45 to 560 kW, while ACS800-U4 modules cover 60 to 600 hp.
Wait 5 minutes so the intermediate circuit capacitors can discharge.
The minimum bend radius is 35 mm (1.4 in).
Retest the safety circuit operation according to the startup instructions.