This manual provides installation, operation, and maintenance instructions for ABB 1TFL 328 241 low voltage systems, including periodic inspection schedules…
The document serves as a guide for the installation, operation, and maintenance of ABB Control Oy Low Voltage Systems, specifically model 1TFL 328 241. It outlines critical safety protocols, such as the prohibition of using defective equipment and the immediate elimination of electrical defects to ensure personnel and property safety.
The manual details specific periodic inspection requirements based on the age of the plant and environmental conditions. Key inspection items include checking earthing conductors every 3-7 years, over-current protection settings every 5 years, and internal switchboard earthings. It also lists general visual inspection criteria, environmental limits (e.g., room temperature ≤ 35°C, relative humidity ≤ 50%), and mechanical function checks for doors and lockings.
| Max. room temperature | ≤ 35°C |
|---|---|
| Max. relative humidity | ≤ 50 % at 40 °C |
| Max. temperature inside switchboard | ≤ 60 °C |
| Min. clearance | ≥ 8 mm |
| Min. creepage distance | ≥ 12,5 mm |
The condition of the earthing conductor should be checked after 3-7 years.
The condition and settings of over-current protection should be checked after 5 years.
If otherwise not recommended, the inspection is carried out once a year.