ABB 16EmaxPower fixed 4-pole UL circuit breakers cover 800 to 5000 amps with manually operated standard features including a PR111 trip unit.
This document covers ABB 16EmaxPower fixed 4-pole UL low-voltage circuit breakers. Models range from E1B-A08 at 800 amps to E6V-A50 at 5000 amps, with interrupting ratings from 42 kA to 125 kA at 480 V.
Standard features on manually operated UL breakers include rear horizontal terminals, a PR111 trip unit with LI protection functions, manual mechanical close and open pushbuttons, mechanical position and spring-charge indicators, auxiliary contacts, lifting plates, current transformers, and a terminal box.
| Pole configuration | 4 pole |
|---|---|
| Operation type | Manually operated |
| Trip unit | PR111 with LI protection |
| Auxiliary contacts | 2NO & 2NC |
| Neutral pole rating E1-E3 | 100% rating |
| Neutral pole rating E4-E6 | 50% rating |
They include rear horizontal terminals, a PR111 trip unit with LI protection functions, mechanical indicators, auxiliary contacts, lifting plates, current transformers, and a terminal box.
The neutral pole rating is 100% of the breaker rating.
The neutral pole rating is 50% of the breaker rating.
ABB Inc. provides the information.