The D1000 is a stand-alone, high speed arc protection unit for electrical power distribution systems. It supports point and fiber sensor technologies for optical arc detection, has inputs for up to six sensors, and generates a tripping pulse in less than 1 millisecond after detecting an arc fault. The relay can be powered from AC or DC and includes 3-phase current measurement, self-supervision, USB event logging, and a Link function for up to four D1000 units.
This manual covers installation, power supply options, the Link interface, sensor inputs and placement, the current sensor, auxiliary inputs, outputs, LEDs and buttons, PC configuration, event logging, commissioning, and specifications.
| Sensor inputs | Up to 6 |
|---|---|
| Arc fault trip pulse time | Less than 1 ms |
| Trip circuit switch type | Solid state switch (IGBT) |
| AC supply voltage | 85–265 V |
| DC supply voltage, 100–250 V range | 85–300 V |
| DC supply voltage, 12–48 V range | 8–60 V |
| Battery supply | 24 V DC (Gel Cell) |
| Link capacity | Up to 4 D1000 modules |
| Current measurement | 3-phase |
| Point sensor signal calibration | 0.5 mA/klux |
The D1000 has inputs for up to six sensors.
It generates a tripping pulse in less than 1 millisecond.
Up to four D1000 units can be connected together, giving a total of 24 sensor inputs.
Yes, the D1000 can be powered from either a DC or AC source.