The Zhuoya Electric Power YHL-100B Loop Resistance Tester is a device used to measure contact resistance in power systems. It uses a high current test method to detect defects in the cross-sectional area of the loop conductor. When measuring the contact resistance of the conductive loop of a high-voltage switch, it is not affected by the oil film and oxide layer between the contacts, and the measurement value is more accurate.
This is the Chinese user manual (使用说明书) for the YHL-100B loop resistance tester (回路电阻测试仪) from Wuhan Zhuoya Electric Power Automation Co., Ltd. The instrument is designed for high-precision measurement of contact (loop) resistance in high-voltage switchgear, in line with the requirement that circuit breaker and disconnector contact resistance be measured with a DC current of at least 100A, and is built to the DL/T845.4-2004 standard using high-frequency switching power supply and digital circuit technology.
The manual covers the instrument's purpose, performance features, technical specifications, panel layout, four-wire (current-voltage method) working principle, step-by-step operating instructions with four-terminal wiring diagrams, troubleshooting of common faults, safety precautions, the packing list, plus appendices on contact resistance basics and standard reference values of conducting loop resistance for various circuit breaker models. This manual is written in Chinese.
| Test current | DC 50A / 100A, two fixed output levels |
|---|---|
| Display | 3½-digit LCD |
| Working power supply | AC 220V ±10%, 50Hz |
| Working environment | Temperature -10°C to 40°C; humidity ≤80%RH |
| Dimensions | 380 × 350 × 260 mm |
| Weight | 5 kg (excluding accessories) |
A display of 1 means the measured loop resistance is over the measurement range (超量程).
No, the instrument must not be used to test loop resistance in energized (live) circuits.
Use the four-terminal method: clamp the current leads on the outside of the test object and the voltage leads on the inside, with current and voltage of the same polarity.