This manual details the features and usage methods of the GM-15kV adjustable high-voltage digital megohmmeter.
This manual provides detailed instructions for operating the GM-15kV adjustable high-voltage digital megohmmeter, designed for measuring insulation resistance in high-voltage environments. It includes safety precautions, operational guidelines, technical specifications, and wiring diagrams for transformer and cable testing. The device features adjustable voltage outputs, wide measurement ranges, and anti-interference capabilities for accurate testing in challenging conditions.
The manual also outlines maintenance and safety protocols, including grounding requirements, proper handling of test leads, and procedures for safe shutdown. It references industry standards such as DL/T 845.1-2004 and DT 474.1-2006, and includes diagrams for practical field applications. This manual is written in Chinese.
| Voltage Output | 0.01~15kV |
|---|---|
| Resistance Range | 0.01MΩ ~ 1999GΩ |
| Accuracy | ±(5%+5 digits) for 20MΩ/500V, ±(5%+5 digits) for 200MΩ/1000V, ±(5%+5 digits) for 2GΩ, ±(5%+5 digits) for 20GΩ, ±(10%+10 digits) for 200GΩ, ±(20%+10 digits) for 2000GΩ |
| Anti-Interference Capability | 2mA (50Hz) |
| Timer Function | Up to 19 minutes 59 seconds, 20-minute cycle |
The maximum voltage output is 15kV, with adjustable voltage from 0.01~15kV.
The resistance measurement range is from 0.01MΩ to 1999GΩ.
The anti-interference capability is 2mA at 50Hz.
The timer function lasts up to 19 minutes 59 seconds, with a 20-minute cycle.