This document provides installation instructions for Dell UPS products.
This document provides installation instructions for Dell UPS models MRVDY, 913CC, and 6WWDY. It warns that only qualified service personnel, such as a licensed electrician, should perform the electrical installation, and that utility power must be switched off at the distribution point before connecting the UPS.
The guide includes a table for installing the optional power cord on specific Dell UPS models and wattage ratings. It also specifies input wiring details, including ground, neutral, and line terminals, wire sizes of 5.26–16 mm2 (10–6 AWG), and a tightening torque of 2.26 Nm (20 lb in).
| Wire Size | 5.26–16 mm2 (10–6 AWG) |
|---|---|
| Tightening Torque | 2.26 Nm (20 lb in) |
| Input Ground Terminal | G |
| Neutral Input Terminal | L2/Neutral In |
| Line Input Terminal | L1/Line In |
MRVDY 4200W 208 Vac UPS, 913CC 3750W, 4200W, or 5600W 230 Vac UPS, and 6WWDY 4200W or 5600W 230 Vac UPS use the optional power cord.
The 5600W Online UPS must not use the optional power cord.
The tightening torque is 2.26 Nm (20 lb in).
Use wire sizes from 5.26–16 mm2 (10–6 AWG).