Dell UPS MRVDY 913CC 6WWDY Installation Guide

This document provides installation instructions for Dell UPS products.


Dell UPS MRVDY 913CC 6WWDY Installation Guide - cover page
Brand
DELL
Category
Other Electronics
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
855 KB
Published
25 November, 2023
Updated
25 November, 2023
Models
913CC, 6WWDY
MD5 checksum
97B67C0C6C00FA1FB213F6B8DDFA8FE9

About this manual

This document provides installation instructions for Dell UPS models MRVDY, 913CC, and 6WWDY. It warns that only qualified service personnel, such as a licensed electrician, should perform the electrical installation, and that utility power must be switched off at the distribution point before connecting the UPS.

The guide includes a table for installing the optional power cord on specific Dell UPS models and wattage ratings. It also specifies input wiring details, including ground, neutral, and line terminals, wire sizes of 5.26–16 mm2 (10–6 AWG), and a tightening torque of 2.26 Nm (20 lb in).

What's inside

  • Power Cord Installation
  • Wire Function
  • Terminal Position
  • Wire Size Rating
  • Tightening Torque
  • Input Ground
  • L2/Neutral In
  • L1/Line In

Specifications

Wire Size5.26–16 mm2 (10–6 AWG)
Tightening Torque2.26 Nm (20 lb in)
Input Ground TerminalG
Neutral Input TerminalL2/Neutral In
Line Input TerminalL1/Line In

Frequently asked questions

Which Dell UPS models use the optional power cord?

MRVDY 4200W 208 Vac UPS, 913CC 3750W, 4200W, or 5600W 230 Vac UPS, and 6WWDY 4200W or 5600W 230 Vac UPS use the optional power cord.

Which UPS model must not use the optional power cord?

The 5600W Online UPS must not use the optional power cord.

What is the tightening torque for UPS input terminals?

The tightening torque is 2.26 Nm (20 lb in).

What wire size is required for input connections?

Use wire sizes from 5.26–16 mm2 (10–6 AWG).

Download PDF (855 KB)

More DELL Manuals


View all DELL manuals →