Dell Online Rack UPS 3750W and 4200W User Guide

Dell Online Rack UPS 3750W and 4200W User’s Guide K804N, H952N, 746FR (DellR4200OLHVUS), J730N, K805N J739N


Dell Online Rack UPS 3750W and 4200W User Guide - cover page
Brand
DELL
Category
Power Management
Document type
User Manual
Language
Chinese
Pages
70
File format
PDF
File size
1.9 MB
Published
22 November, 2023
Updated
22 November, 2023
Model
3750W
MD5 checksum
53878666D97F3A6D7CEE9098CABF7541

About this manual

This user guide covers Dell online rack UPS models rated 3750 W and 4200 W. It describes safety warnings, unpacking, rack installation, external battery module installation, hardwired input, initial startup, operation, control panel functions, settings, maintenance, specifications, and troubleshooting.

The UPS uses an online double-conversion design with pure sine wave output and can operate in an optional high-efficiency mode. It supports battery startup without utility power, can connect to one external battery module, provides remote emergency power off, has USB and DB-9 serial ports, supports an optional Dell network management card, load segments, and firmware upgrades without a service call. This manual is written in Chinese.

What's inside

  • Introduction
  • Safety Warnings
  • Installation
  • Operation
  • Other UPS Features
  • UPS Maintenance
  • Specifications
  • Troubleshooting

Specifications

Output power ratings3750 W and 4200 W
Model numbersK804N, H952N, 746FR (DellR4200OLHVUS), J730N, K805N; EBM J739N
UPS dimensions438.0 x 171.5 x 801.4 mm (17.2 x 6.8 x 31.5 in), 4U
EBM dimensions438.0 x 127.0 x 735.0 mm (17.2 x 5.0 x 29.0 in), 3U
UPS weight66.0 kg (145.5 lb)
EBM weight53.0 kg (116.8 lb)
EBM rating192 Vdc / 30 A
Input wiring size5.26-16 mm2 (10-6 AWG)
Input terminal torque2.26 Nm (20 lb in)
Branch-circuit protection3750 W: 208 V 30 A, 230 V 25 A; 4200 W: 200 V 30 A, 208 V 30 A, 230 V 30 A
Maximum ambient temperature40 C (104 F)

Frequently asked questions

What electrical problems does this UPS protect against?

It protects sensitive electronic equipment from outages, voltage sags, surges, undervoltage, and line interference.

Can the UPS start from battery without utility power?

Yes. The battery startup function can power the UPS even when utility power is unavailable.

How many external battery modules can be connected?

The UPS can connect with up to one external battery module (EBM).

What is the maximum operating temperature?

The ambient temperature must not exceed 40 C (104 F).

Download PDF (1.9 MB)