Nanjing YingLeike EIR-RDHL-5/EIR-RDHL-A Digital DC Over-current and Under-current Relay User Manual

This product is a digital DC current relay with over-current and under-current protection functions. The over-current and under-current setting range is the measurement range. The setting value and delay time are set through the panel keys. It can also be used as a digital DC ammeter or as a load control relay.


Nanjing YingLeike EIR-RDHL-5/EIR-RDHL-A Digital DC Over-current and Under-current Relay User Manual - cover page
Brand
南京英雷科电子
Category
RELAY
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
123 KB
Published
18 November, 2023
Updated
18 November, 2023
MD5 checksum
121DC346CF0716BF5A189BBF1E8E96D2

About this manual

This manual describes a digital DC current relay with over-current and under-current protection. It can also be used as a digital DC ammeter or load control relay, supports automatic or manual reset, and captures maximum and minimum measured current values.

The document includes technical parameters, parameter settings and debugging steps, shunt configuration, terminal wiring, and a parameter setting example. Settings such as over-current value, under-current value, delay times, shunt rated current, shunt rated voltage drop, and reset mode are adjusted through the front-panel keys. This manual is written in Chinese.

What's inside

  • Product functions
  • Technical parameters
  • Parameter settings and debugging
  • Parameter modification
  • Other functions
  • Shunt configuration
  • Terminal wiring

Specifications

Measurement range (EIR-RDHL-5)0.00-5.00 A
Output relay capacity3 A/250 VAC or 3 A/30 VDC (resistive load)
Auxiliary power supply85-265 VAC or 110-360 VDC
Dimensions53 mm x 88 mm x 58 mm
Output relay contacts1 NO and 1 NC with common terminal

Frequently asked questions

How is the relay reset manually?

When the measured current returns to a normal value, press the reset key to restore the output relay to its normal state.

What happens if the over-current or under-current settings are invalid?

The setting window displays "F", and the SET key must be pressed again to re-enter the settings.