CONTECH FSTH Thermal Flow and Level Switch Installation and Operation Manual

The FSTH thermal flow and level switch operates on the principle of thermal dispersion. Two RTD temperature sensor elements are arranged side by side at the end of a pipe. As fluid flows past the sensors, it carries heat away from the heated sensor. By measuring the temperature difference between the two sensors, the flow rate can be determined.


CONTECH FSTH Thermal Flow and Level Switch Installation and Operation Manual - cover page
Brand
Contech
Category
flow transmitter
Document type
User Manual
Language
Portuguese
Pages
9
File format
PDF
File size
128 KB
Published
17 November, 2023
Updated
17 November, 2023
MD5 checksum
AF4E2B7EAE119F0AF80E9C0D4580E52C

About this manual

The CONTECH FSTH is a thermal flow and level switch that uses two RTD temperature sensors and thermal dispersion to detect flow or level in liquids and gases. It switches a DPDT relay output based on an adjustable setpoint.

This manual provides installation, wiring, configuration, adjustment, cleaning, and troubleshooting instructions for the FSTH switch, including dimensions, electrical connections, and operating modes. This manual is written in Portuguese.

What's inside

  • Introduction
  • Operating Principle
  • Dimensions
  • Specifications
  • Mounting
  • Connections
  • Configuration and Adjustment
  • Sensor Cleaning
  • Troubleshooting

Specifications

Repeatability± 1% of setting
Liquid range0.005 to 1 mps
Gas range0.3 to 30 nmps
Response time2 to 20 seconds
Power supply24Vdc (23 to 28 Vdc) or 115/230 Vac ±10%, 50 to 60Hz
Output signalDPDT relay 5A x 250Vac / 5A 30Vdc
EnclosureCast aluminum or stainless steel explosion-proof, IP66
Electrical connection3/4" NPT
Max pressure3000 PSI
Sensor temperature-40 to 150°C

Frequently asked questions

How does the CONTECH FSTH thermal flow and level switch detect flow and level?

It uses two RTD temperature sensors and thermal dispersion; electronics compares the temperature difference between the two elements to the actuation setpoint to switch the relay.

What operating modes are available on the FSTH switch?

Jumper J3 position H selects maximum flow or level detection; position L selects minimum flow.

How is the actuation point adjusted on the FSTH?

Set the flow or level, turn trimpot R18 until the LED turns off, then slowly turn it clockwise until the LED turns on.

What should be done if fuse F1 blows?

Replace it with the same capacity (100mA for 115 Vac, 50mA for 230 Vac or 200mA for 24 Vdc); if it blows again, contact technical support.

Download PDF (128 KB)